What is NSGAFÖU Cable


NSGAFÖU Cable is a single core flexible rubber cable for power and general wiring. It is widely used in Automation & Process Control industry, in switch cabinets and to wire general devices with a voltage rating of 1.8/3kV. NSGAFÖU Cable is short-circuit proof and is recommended for wiring railway vehicles (rolling stock) and buses for earth-fault-proof routing.
 

NSGAFÖU Cable Construction:


Cores: Of tinned copper wires, multi-wire flexible classes 5 according to DIN-EN 60228
Insulation: EPR rubber compound type 3GI3 according to DIN VDE 0207 part 20
Insulation color: Natural
Outer coverage: 5GM3 flame retardant and oil resistant compound according to DIN VDE 0207 part 21
The color of the outer cover: Black
 

NSGAFÖU Cable Construction Data: 


Cross section Current carrying capacity in free air ** Short circuit current ( t = 1s )
***
Nominal diameter of conductor Conductor resistance at 20 °C (acc.to
IEC 60228)
Minimum outer Ø Maximum outer Ø Approx weight
N ° x mm2 [A] [kA] [mm] [/km] [mm] [mm] [kg/km]
1 × 1,5 31 0.2 1.5 13.7 5.5 7 50
1 × 2,5 42 0.33 1.9 8.21 5.9 7.5 65
1 × 4 55 0.53 2.4 5.09 6.4 8 80
1 × 6 70 0.79 3 3.39 7 8.6 105
1 × 10 99 1.32 3.9 1.95 8.2 10 155
1 × 16 130 2.11 4.9 1.24 9.2 11.1 215
1 × 25 173 3.3 6 0.795 11.3 13.4 330
1 × 35 214 4.62 7.2 0.565 12.5 14.6 430
1 × 50 270 6.6 8.6 0.393 14.1 16.4 590
1 × 70 340 9.24 10.3 0.277 15.9 18.3 785
1 × 95 410 12.54 12.5 0.21 18.2 20.8 1030
1 × 120 487 15.84 14.2 0.164 19.6 22.4 1300
1 × 150 562 19.8 15.8 0.132 21.7 24.7 1560
1 × 185 644 24.42 17.5 0.108 23.6 26.7 1930
1 × 240 775 31.68 20.1 0.0817 26.3 29.7 2390
1 × 300 895 39.6 22.9 0.0654 29.3 32.9 3040
1 x 400 1079 52.8 25.9 0.0495 32.5 36.4 3960
1 x 500 1260 52.8 28.9 0.0391 36.5 40.7 5150

 

NSGAFÖU Cable Characteristics:


Maximum conductor temperature during cable operation: +90°C
Minimum ambient temperature for permanently laid cables: -40°C
Minimum ambient temperature for cable laying: -25°C
Maximum core temperature during short circuit: +250°C
Minimum bending radius: 5x outer diameter of the wire
Standard packaging: On drums of 500 or 1000 m. It is possible to offer other lengths of sections and types of packaging.


Any cable inquiry please feel free to contact us.